How to Read Load-Span Tables

Table structure, deflection limits, safety factors, interpolation and worked examples

Table Anatomy

What a Load-Span Table Actually Shows

A load/span table is a two-way lookup. The rows are the panel options (thickness, mesh or bearing-bar series). The columns are the clear spans you might use. The value in each cell is the allowable load (uniformly distributed load, UDL, in kN/m2 or psf) that the panel carries at a stated deflection limit. A well-formed table states the deflection limit, the safety factor and the support condition on its face - read those first.

Panel optionSpan 0.6 mSpan 0.9 mSpan 1.2 mSpan 1.5 m
25 mm moldedallowable UDLallowable UDLallowable UDLallowable UDL
38 mm moldedallowable UDLallowable UDLallowable UDLallowable UDL
50 mm moldedallowable UDLallowable UDLallowable UDLallowable UDL
Pultruded I/T-barallowable UDLallowable UDLallowable UDLallowable UDL

Annotated structure: pick your panel row, move to your span column, and read the allowable UDL. If your required load is below the cell value (at your deflection limit), the panel works.

UDL vs Concentrated

Two Loads, Two Tables

Uniformly Distributed Load (UDL)

Load spread over the whole area, in kN/m2 or psf. A crowd, a material layer, an equipment mat. Most tables default to UDL at a given deflection limit.

Concentrated Load

A single point load, in kN or lbf - a forklift wheel, a machine foot. Checked on a separate concentrated-load table; a panel fine for UDL can deflect badly under one wheel.

Never compare a UDL table value with a concentrated load. They use different load cases and acceptance criteria; ask for the concentrated-load table if you have wheels or feet.

Deflection & Safety

Deflection Limits and Built-In Safety Factors

LimitDeflection AllowedTypical Use
L/100Span / 100General industrial walkways, less sensitive
L/150Span / 150Standard pedestrian platforms, balconies
L/200Span / 200Sensitive areas, machinery decks, high-crowd

Safety Factor

ZeAllgrate load tables are working-load charts: they already include a safety factor of roughly 4:1 (molded) to 5:1 (pultruded) over ultimate, per ZeAllgrate practice. Do not divide the value again.

Same Panel, Different Limit

A stricter limit (L/200 vs L/100) lowers the allowable load on the same panel. Always read the table at the deflection limit your project specifies - the same number means different things.

Interpolation

Reading Between the Lines

Tables step spans in fixed increments (e.g. 0.6, 0.9, 1.2, 1.5 m). For an in-between span, interpolate linearly between the two adjacent cells on the same row. Because deflection scales with span cubed and strength with span squared, linear interpolation is conservative and acceptable for selection; for a critical design, ask ZeAllgrate engineering to compute the exact value.

StepAction
1Find your required UDL and your clear span.
2Locate the two nearest span columns that bracket your span on the chosen panel row.
3Linearly interpolate the allowable load between those two cells.
4Compare the interpolated allowable with your required load; require allowable to exceed required.
5If close (within 10%), choose the next panel up or request a certified chart.
Worked Example 1

Pedestrian Walkway - UDL Selection

GivenValue
Required UDL3.0 kN/m2 (approx. 63 psf pedestrian)
Clear span1.0 m
Deflection limitL/150 (standard pedestrian)
SolutionScan the 38 mm molded row at 0.9 and 1.2 m at L/150; interpolate to 1.0 m. The allowable UDL exceeds 3.0 kN/m2. Select 38 mm molded.
CheckConfirm bearing bars across the span, min 50 mm bearing and 4 clips per panel.
Worked Example 2

Industrial Platform - Heavier Load, Stricter Limit

GivenValue
Required UDL10 kN/m2 (industrial / equipment mat)
Clear span1.5 m
Deflection limitL/200 (sensitive / machinery deck)
SolutionMolded panels at L/200 over 1.5 m cannot carry 10 kN/m2. Move to pultruded I/T-bar at 50 mm class; the pultruded row at 1.5 m, L/200 exceeds 10 kN/m2. Select 50 mm pultruded.
CheckPultruded bars across span, 75 mm bearing, concentrated-load check for any equipment feet.
Worked Example 3

Concentrated Load - Check Both Shear and Deflection

GivenValue
Concentrated load1.5 kN at midspan (machine foot)
Clear span0.9 m
Step 1 - DeflectionLook up the concentrated-load deflection table; ensure midspan deflection stays within L/150/L/200 under the point load.
Step 2 - Shear / bearingCheck end reaction and web crippling at the support (bearing-bar end) against the pultruded web-crippling value and the 150-200 MPa bearing strength.
SolutionChoose a panel whose concentrated-load row passes both deflection and shear/bearing at 0.9 m; if UDL alone passes but the point load does not, upgrade the bar series.
Mistakes & Limits

Common Mistakes and Table Limitations

MistakeWhy It Is WrongCorrect Approach
Using the wrong deflection limitL/100 values look stronger than L/200Use the limit the project specifies
Ignoring concentrated loadsUDL-fine panels can fail under one wheelRun the concentrated-load table too
Forgetting impact / dynamic loadForklifts and vibrating equipment amplify loadApply 1.25-2.0 impact factor before comparing
Re-applying the safety factorTables already include 4:1-5:1Compare required load directly with table value
Pultruded bars parallel to spanPanel becomes weak along the wrong axisBearing bars MUST cross the clear span

Table Assumptions

Published values assume simply supported, uniformly distributed load, standard bearing length and room temperature. Continuous spans, cantilevers, impact and high temperature need engineering adjustment.

When to Call an Engineer

Cantilevers, irregular cut-outs, combined UDL plus heavy point loads, temperature above 40 C, or any case close to a table limit - send the load list to ZeAllgrate for a certified chart.

Need Certified Load/Span Tables for Your Project?

Send clear span, UDL, any point load and deflection limit - ZeAllgrate returns the exact panel and chart reference.

Source: ZeAllgrate (Fiberglass Grating Manufacturers Council / ACMA) design guidelines; ASTM International; ISO 14122; OSHA 29 CFR 1910. Indicative data for specification guidance only — final design verified by ZeAllgrate engineering against certified load/span charts.